Addr.
Setting Title
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest
3430
AR TRIP 3pole
3431
DLC or RDT
3438
T U-stable
3440
U-live>
3441
U-dead<
3420
AR w/ DIST.
3421
AR w/ SOTF-O/C
3422
AR w/ W/I
3423
AR w/ EF-O/C
3424
AR w/ DTT
3425
AR w/ BackUpO/C

6.12.4 Information Overview

7SA6 Manual
C53000-G1176-C133-1
Setting Options
0.01..1800.00 sec; ∞
0.01..1800.00 sec
YES
NO
YES
NO
YES
NO
Without
Reduced Dead Time (RDT)
Dead Line Check (DLC)
0.10..30.00 sec
30..90 V
2..70 V
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
The most important information about automatic reclosure is briefly explained
insofar as it was not mentioned in the following lists or described in detail in the
preceding text.
"!%/. $5F\FOH" (F.No. ) to "!%/. Q $5" (F.No. )
The corresponding reclose cycle is blocked. If the blocking state already exists when
the automatic reclosure function is initiated, the blocked cycle is not executed and may
be skipped (if other cycles are permitted). The same applies if the automatic
reclosure function is started (running) but not busy with (inside) the cycle being
blocked. If the block signal of a cycle appears while this cycle is being executed (busy)
the automatic reclosure function is blocked dynamically; no further automatic
reclosures cycles are then executed.
"$5 &\F=RQH5HO" (F.No. 2889) to "$5 &\F=RQH5HO" (F.No. )
The automatic reclosure function is ready for the corresponding reclosure cycle. This
Default Setting
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before
reclosing
NO
Request for synchro-check after
3pole AR
YES
3pole TRIP by AR
Without
Dead Line Check or Reduced
Dead Time
0.10 sec
Supervision time for dead/ live
voltage
48 V
Voltage threshold for live line or
bus
30 V
Voltage threshold for dead line
or bus
YES
AR with distance protection
YES
AR with switch-onto-fault over-
current
YES
AR with weak infeed tripping
YES
AR with earth fault overcurrent
prot.
YES
AR with direct transfer trip
YES
AR with back-up overcurrent
Functions
Comments
6-193