Installation and Commissioning
8-24
Table 8-10
Jumper setting of control voltages of binary inputs BI6 to BI29 on the binary in-
put/output boards C– I/O–1 for housing size
Binary input
Slot 33
Slot 19
left
right
BI6
BI14
BI7
BI15
BI8
BI16
BI9
BI17
BI10
BI18
BI11
BI19
BI12
BI20
BI13
BI21
1
) Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2
) Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115 VAC
The jumpers X71, X72 and X73 on the input/output board C–I/O–1 are for setting the
bus address and must not be changed. Tables 8-11 and 8-12 list the jumper
presettings.
Figures 8-8 to 8-10 show the mounting location of the printed circuit boards.
Table 8-11
Jumper setting of printed circuit board addresses of binary input/output
boards C-I/O-1 for housing size
Jumper
Mounting
location
Slot 19
X71
H
X72
L
X73
H
Table 8-12
Jumper setting of printed circuit board addresses of binary input/output
boards C-I/O-1 for housing size
Jumper
Slot 19 left
X71
H
X72
H
X73
H
Jumper
Slot 19
left
BI22
X21/X22
BI23
X23/X24
BI24
X25/X26
BI25
X27/X28
BI26
X29/X30
BI27
X31/X32
BI28
X33/X34
BI29
X35/X36
1
/
2
1
/
1
Mounting location
Slot 19 right
L
H
H
1
/
1
Threshold
Threshold
1
2
17 V
)
73 V
)
L
M
L
M
L
M
L
M
L
M
L
M
L
M
L
M
Slot 33 left
H
L
H
C53000-G1176-C133-1
7SA6 Manual