Addr.
Setting Title
1301
Op. mode Z1
1302
R(Z1) Ø-Ø
1303
X(Z1)
1304
RE(Z1) Ø-E
1305
T1-1phase
1306
T1-multi-phase
1307
Zone Reduction
1311
Op. mode Z2
1312
R(Z2) Ø-Ø
1313
X(Z2)
1314
RE(Z2) Ø-E
1315
T2-1phase
1316
T2-multi-phase
1317A
Trip 1pole Z2
1321
Op. mode Z3
1322
R(Z3) Ø-Ø
1323
X(Z3)
1324
RE(Z3) Ø-E
1325
T3 DELAY
7SA6 Manual
C53000-G1176-C133-1
Function
Setting Options
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0..30 °
Distance zones
(quadrilateral)
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
Distance protec-
NO
tion, general set-
YES
tings
Distance zones
(quadrilateral)
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance zones
(quadrilateral)
Default Setting
Forward
Operating mode Z1
1.25 Ohm
R(Z1), Resistance for ph-ph-faults
2.50 Ohm
X(Z1), Reactance
2.50 Ohm
RE(Z1), Resistance for ph-e faults
0.00 sec
T1-1phase, delay for single phase
faults
0.00 sec
T1multi-ph, delay for multi phase faults
0 °
Zone Reduction Angle (load compen-
sation)
Forward
Operating mode Z2
2.50 Ohm
R(Z2), Resistance for ph-ph-faults
5.00 Ohm
X(Z2), Reactance
5.00 Ohm
RE(Z2), Resistance for ph-e faults
0.30 sec
T2-1phase, delay for single phase
faults
0.30 sec
T2multi-ph, delay for multi phase faults
NO
Single pole trip for faults in Z2
Reverse
Operating mode Z3
5.00 Ohm
R(Z3), Resistance for ph-ph-faults
10.00 Ohm
X(Z3), Reactance
10.00 Ohm
RE(Z3), Resistance for ph-e faults
0.60 sec
T3 delay