Teleprotection Schemes With Distance Protection - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.4

Teleprotection Schemes with Distance Protection

Purpose of
Teleprotection
Teleprotection
Schemes
Signal
Transmission
Channels
7SA6 Manual
C53000-G1176-C133-1
Short-circuits which occur on the protected line, beyond the first distance zone, can
only be cleared selectively by the distance protection after a delay time. On line
sections that are shorter than the smallest sensible distance setting, short-circuits can
also not be selectively cleared instantaneously.
To achieve non-delayed and selective tripping on 100 % of the line length for all faults
by the distance protection, the distance protection can exchange and process
information from the opposite line end by means of signal transmission systems. For
this purpose, the device has signal send outputs and receive inputs as well as
associated logic functions.
The distance protection is set with normal zone grading characteristic. An additional
fast overreaching zone Z1B is available for teleprotection schemes. Signal
transmission and trip release methods depend on the teleprotection scheme. At least
one reverse looking distance zone may be required for some teleprotection schemes.
It is recommended to use zone Z3 for this purpose.
The 7SA6 permits:
• PUTT (Pickup)
• Permissive Underreach Transfer Trip with Zone Acceleration Z1B (PUTT)
• Direct Transfer Trip without Pickup
In the comparison scheme of the distance protection an accelerated overreach zone
applies from the outset. It can only trip if a fault is also recognized at the other line end
in an overreach zone. A release signal or a blocking signal is transmitted. The
following are available:
Release scheme:
• Permissive Overreach Transfer Trip (POTT)
• Directional Comparison Pickup
• Unblocking with Overreach Zone Z1B
Blocking scheme:
• Blocking with Overreach Zone Z1B
Schemes via pilot wire:
• Pilot Wire Comparison
• Reverse Interlocking
As the distance zones Z1 ... Z5 (without Z1B) function independently, instantaneous
tripping in Z1 without a release signal is always possible. If instantaneous tripping in
Z1 is not required (e.g. in very short lines), then Z1 must be delayed with T1.
The pilot wire comparison, that is exclusively applied to short tie lines, enables the
user to operate a pilot wire pair (pilot wires or control wires) with direct current to
guarantee the exchange of information between the line ends. Also the reverse
interlocking operates with DC control signals.
Functions
6-75