Siemens siprotec 7SA6 User Manual page 325

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Definite Time
Overcurrent
Stage I>
Inverse Time
Overcurrent
Stage I
p
7SA6 Manual
C53000-G1176-C133-1
Dƒu33
!% 
I
L1
Iph>
I
L2
I
L3
L1
L2
L3
!% ! "D33
I
E
3I0>>
E
7104 >BLOCK O/C I>>
!% #
7110 >O/C InstTRIP
T
0
Switch onto
fault
!% $
!%' TPUAÃUv€rÃ9@G6`
further
stages
Figure 6-83
Logic diagram of the I>>–stage
The logic of the overcurrent stage I> is the same as that of the I>>–stage. All
references to Iph>> must simply be replaced by ,SK! and 3I0>> by ,!. In all other
respects Figure 6-83 applies.
The logic of the inverse overcurrent stage also in principal functions the same as the
remaining stages. The time delay in this case however results from the nature of the
set characteristic (parameter ,(& &XUYH), the magnitude of the current and the time
multiplier (Figure 6-84). A pre-selection of the available characteristics was already
done during the configuration of the protection functions. Furthermore, an additional
constant time delay 7 ,S $GG (address ) may be selected, which are added to
the current dependant time derived from the IDMT characteristic. The available
characteristics are shown in the technical data, Section 10.5, Figure 10-1 to 10-3.
Figure 6-84 shows the logic diagram. The setting parameter addresses of the IEC
characteristics are shown by way of an example. In the setting information (Sub-
section 6.9.2) the different setting addresses are elaborated upon.
!%
UÃDƒu33Ã
T
0
&
&
!% " UÃ"D33
T
0
&
&
D33ÃUryrƒ7D
Yes
≥1
No
Yes
No
D33ÃTPUA
Functions
I>> Pickup L1
I>> Pickup L2
I>> Pickup L3
≥1
I>> Trip L1
I>> Trip L2
I>> Trip L3
I>> Pickup E
≥1
I>> Trip E
I>> Anr L1
6-143

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents