Settings - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.5.3

Settings

Addr.
Setting Title
3101
FCT EarthFltO/C
3102
BLOCK for Dist.
3103
BLOCK 1pDeadTim YES
3104A
Iph-STAB. Slope
3105A
3IoMin Teleprot
3105A
3IoMin Teleprot
3170
2nd InrushRest
3171
Imax InrushRest
3172
SOTF Op. Mode
3173
SOTF Time DELAY
3110
Op. mode 3I0>>>
3111
3I0>>>
3112
T 3I0>>>
3113
3I0>>> Telep/BI
3114
3I0>>>SOTF-Trip
3115
3I0>>>InrushBlk
3120
Op. mode 3I0>>
3121
3I0>>
3122
T 3I0>>
3123
3I0>> Telep/BI
7SA6 Manual
C53000-G1176-C133-1
Note: The indicated secondary current values for setting ranges and default settings
refer to I
= 1 A. For the nominal current 5 A the current values are to be multiplied
N
by 5.
Setting Options
ON
OFF
with every Pickup
with single-phase Pickup
with multi-phase Pickup
NO
NO
0..30 %
0.01..1.00 A
0.003..1.000 A
10..45 %
0.50..25.00 A
with Pickup (non-directional)
with Pickup and direction
0.00..30.00 sec
Forward
Reverse
Non-Directional
Inactive
0.50..25.00 A
0.00..30.00 sec; ∞
NO
YES
NO
YES
NO
YES
Forward
Reverse
Non-Directional
Inactive
0.20..25.00 A
0.00..30.00 sec; ∞
NO
YES
Default Setting
ON
Earth Fault overcurrent function
is
with every Pickup
Block E/F for Distance protection
NO
Block E/F for 1pole Dead time
10 %
Stabilisation Slope with Iphase
0.50 A
3Io-Min threshold for Teleprot.
schemes
0.500 A
3Io-Min threshold for Teleprot.
schemes
15 %
2nd harmonic ratio for inrush
restraint
7.50 A
Max.Current, overriding inrush
restraint
with Pickup and
Instantaneous mode after
direction
SwitchOnToFault
0.00 sec
Trip time delay after SOTF
Inactive
Operating mode
4.00 A
3I0>>> Pickup
0.30 sec
T 3I0>>> Time delay
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Switch-
OnToFault
NO
Inrush Blocking
Inactive
Operating mode
2.00 A
3I0>> Pickup
0.60 sec
T 3I0>> Time Delay
NO
Instantaneous trip via Teleprot./
BI
Functions
Comments
6-117