Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
1126
RM/RL ParalLine
1127
XM/XL ParalLine
1128
RATIO Par. Comp
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1132A
SI Time all Cl.
1134
Line Closure
1135
Reset Trip CMD
1140A
I-CTsat. Thres.
1150A
SI Time Man.Cl
1151
SYN.MAN.CL
1155
3pole coupling
1156A
Trip2phFlt
6.1.3.2

Information Overview

F.No.
Alarm
351
>CB Aux. L1
352
>CB Aux. L2
353
>CB Aux. L3
379
>CB 3p Closed
380
>CB 3p Open
356
>Manual Close
357
>Close Cmd. Blk
361
>FAIL:Feeder VT
362
>FAIL:Bus VT
7SA6 Manual
C53000-G1176-C133-1
Function
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
>Circuit breaker aux. contact: Pole L1
>Circuit breaker aux. contact: Pole L2
>Circuit breaker aux. contact: Pole L3
>CB aux. contact 3pole Closed
>CB aux. contact 3pole Open
>Manual close signal
>Block all Close commands from external
>Failure: Feeder VT (MCB tripped)
>Failure: Busbar VT (MCB tripped)
Setting Options
0.00..8.00
0.00..8.00
50..95 %
0.05..1.00 A
2..70 V
0.01..30.00 sec
Manual Close BI only
Current OR Voltage or
Manual close BI
CBaux OR Current or
Manual close BI
Current flow or Manual
close BI
with Pole Open Current
Threshold only
with CBaux AND Pole
Open Current
0.2..50.0 A; ∞
0.01..30.00 sec
with Synchronism-check
without Synchronism-
check
NO
with Pickup
with Trip
3pole
1pole, leading phase
1pole, lagging phase
Comments
Functions
Default Setting
0.00
0.00
85 %
0.10 A
30 V
0.05 sec
Manual Close BI only
with Pole Open Current
Threshold only
10.0 A
0.30 sec
without Synchronism-check
with Trip
3pole
6-25