Addr.
Setting Title
1341
Op. mode Z5
1342
R(Z5) Ø-Ø
1343
X(Z5)+
1344
RE(Z5) Ø-E
1345
T5 DELAY
1346
X(Z5)-
7SA6 Manual
C53000-G1176-C133-1
Setting Options
Forward
Reverse
Non-Directional
Inactive
0.05..250.00 Ohm
0.05..250.00 Ohm
0.05..250.00 Ohm
0.00..30.00 sec; ∞
0.05..250.00 Ohm
Default Setting
Inactive
Operating mode Z5
12.00 Ohm
R(Z5), Resistance for ph-ph-
faults
12.00 Ohm
X(Z5)+, Reactance for Forward
direction
12.00 Ohm
RE(Z5), Resistance for ph-e
faults
0.90 sec
T5 delay
4.00 Ohm
X(Z5)-, Reactance for Reverse
direction