Siemens siprotec 7SA6 User Manual page 726

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Appendix
B.1
Settings
Please see " Note " for settings right at the end of Section B.1
Addr.
Setting Title
103
Grp Chge OPTION Scope of Functions Disabled
110
Trip mode
114
Dis. PICKUP
120
Power Swing
121
Teleprot. Dist.
122
DTT Direct Trip
124
SOTF Overcurr.
125
Weak Infeed
126
Back-Up O/C
130
Sens. Earth Flt
131
Earth Fault O/C
132
Teleprot. E/F
133
Auto Reclose
134
AR control mode
135
Synchro-Check
137
Overvoltage
B-2
Function
Setting Options
Enabled
Scope of Functions 3pole only
1-/3pole
Scope of Functions Z< (quadrilat.)
I> (overcurr.)
U/I
U/I/<phi>
Disabled
Scope of Functions Disabled
Enabled
Scope of Functions PUTT (Z1B)
PUTT (Pickup)
POTT
Dir.Comp.Pickup
UNBLOCKING
BLOCKING
Rev. Interlock
Pilot wire comp
Disabled
Scope of Functions Disabled
Enabled
Scope of Functions Disabled
Enabled
Scope of Functions Disabled
Enabled
Scope of Functions Disabled
TOC IEC
TOC ANSI
Scope of Functions Disabled
Enabled
Scope of Functions Disabled
TOC IEC
TOC ANSI
TOC Logarithm.
Definite Time
U0 inverse
Scope of Functions Dir.Comp.Pickup
UNBLOCKING
BLOCKING
Disabled
Scope of Functions Disabled
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Scope of Functions Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Scope of Functions Disabled
Enabled
Scope of Functions Disabled
Enabled
.
Default Setting
Disabled
3pole only
I> (overcurr.)
Disabled
Disabled
Disabled
Disabled
Disabled
TOC IEC
Disabled
Disabled
Disabled
Disabled
Pickup w/ Tact
Disabled
Disabled
Comments
Setting Group Change Option
Trip mode
Distance protection pickup
program
Power Swing detection
Teleprotection for Distance prot.
DTT Direct Transfer Trip
Instantaneous HighSpeed SOTF Over-
current
Weak Infeed (Trip and/or Echo)
Backup overcurrent
Sensitive Earth Flt.(comp/ isol. starp.)
Earth fault overcurrent
Teleprotection for Earth fault overcurr.
Auto-Reclose Function
Auto-Reclose control mode
Synchronism and Voltage Check
Overvoltage

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents