Settings; Information Overview - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
6.6.3

Settings

Addr.
Setting Title
3201
FCT Telep. E/F
3202
Line Config.
3203A
Send Prolong.
3207A
Delay for alarm
3208
Release Delay
3209A
TrBlk Wait Time
3210A
TrBlk BlockTime
6.6.4

Information Overview

F.No.
Alarm
1311
>EF Teleprot.ON
1312
>EF TeleprotOFF
1313
>EF TeleprotBLK
1318
>EF Rec.Ch1
1319
>EF Rec.Ch2
1320
>EF UB ub 1
1321
>EF UB bl 1
1322
>EF UB ub 2
1323
>EF UB bl 2
1324
>EF BlkEcho
1380
EF TeleON/offBI
1381
EF Telep. OFF
1384
EF Tele SEND
1386
EF TeleTransBlk
1387
EF TeleUB Fail1
1388
EF TeleUB Fail2
1389
EF Tele BL STOP
1390
EF Tele BL Jump
6-134
Setting Options
ON
OFF
Two Terminals
Three Terminals
0.00..30.00 sec; Ø
0.00..30.00 sec; Ø
0.000..30.000 sec; Ø
0.00..30.00 sec; Ø; ∞
0.00..30.00 sec; Ø
>E/F Teleprotection ON
>E/F Teleprotection OFF
>E/F Teleprotection BLOCK
>E/F Carrier RECEPTION, Channel 1
>E/F Carrier RECEPTION, Channel 2
>E/F Unblocking: UNBLOCK, Channel 1
>E/F Unblocking: BLOCK, Channel 1
>E/F Unblocking: UNBLOCK, Channel 2
>E/F Unblocking: BLOCK, Channel 2
>E/F BLOCK Echo Signal
E/F Teleprot. ON/OFF via BI
E/F Teleprotection is switched OFF
E/F Telep. Carrier SEND signal
E/F Telep. Transient Blocking
E/F Telep. Unblocking: FAILURE Channel 1
E/F Telep. Unblocking: FAILURE Channel 2
E/F Telep. Blocking: carrier STOP signal
E/F Tele.Blocking: Send signal with jump
Default Setting
ON
Teleprotection for Earth Fault O/
C
Two Terminals
Line Configuration
0.05 sec
Time for send signal prolonga-
tion
10.00 sec
Unblocking: Time Delay for
Alarm
0.000 sec
Time Delay for release after
pickup
0.04 sec
Transient Block.: Duration exter-
nal flt.
0.05 sec
Transient Block.: Blk.T. after ext.
flt.
Comments
Comments
7SA6 Manual
C53000-G1176-C133-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents