Addr.
Setting Title
3141
3I0p PICKUP
3142
3I0p MinT-DELAY
3143
3I0p Time Dial
3144
3I0p Time Dial
3145
3I0p Time Dial
3146
3I0p MaxT-DELAY
3147
Add.T-DELAY
3148
3I0p Telep/BI
3149
3I0p SOTF-Trip
3150
3I0p InrushBlk
3151
IEC Curve
3152
ANSI Curve
3153
LOG Curve
3154
3I0p Startpoint
3182
3U0>(U0 inv)
3183
U0inv. minimum
3184
T forw. (U0inv)
3185
T rev. (U0inv)
3160
POLARIZATION
3162A
Dir. ALPHA
3163A
Dir. BETA
3164
3U0>
7SA6 Manual
C53000-G1176-C133-1
Setting Options
0.003..25.000 A
0.00..30.00 sec
0.05..3.00 sec; ∞
0.50..15.00; ∞
0.05..15.00 sec; ∞
0.00..30.00 sec
0.00..30.00 sec; ∞
NO
YES
NO
YES
NO
YES
Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Logarithmic inverse
1.0..4.0
1.0..10.0 V
0.1..5.0 V
0.00..32.00 sec
0.00..32.00 sec
with U0 and IY (dual polar-
ized)
with IY (transformer star
point current)
with U2 and I2 (negative
sequence)
0..360 °; Ø
0..360 °; Ø
0.5..10.0 V
Default Setting
1.000 A
3I0p Pickup
1.20 sec
3I0p Minimum Time Delay
0.50 sec
3I0p Time Dial
5.00
3I0p Time Dial
1.35 sec
3I0p Time Dial
5.80 sec
3I0p Maximum Time Delay
1.20 sec
Additional Time Delay
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Switch-
OnToFault
NO
Inrush Blocking
Normal Inverse
IEC Curve
Inverse
ANSI Curve
Logarithmic
LOGARITHMIC Curve
inverse
1.1
Start point of inverse character-
istic
5.0 V
3U0> setpoint
0.2 V
Minimum voltage U0min for T-
>oo
0.90 sec
T-forward Time delay (U0inv)
1.20 sec
T-reverse Time delay (U0inv)
with U0 and IY
Polarization
(dual polarized)
338 °
ALPHA, lower angle for forward
direction
122 °
BETA, upper angle for forward
direction
0.5 V
Min. zero seq.voltage 3U0 for
polarizing
Functions
Comments
6-119