6.21.5 Settings

Average
Calculation
Addr.
Setting Title
2801
DMD Interval
2802
DMD Sync.Time
Min/Max Values
Addr.
Setting Title
2811
MinMax cycRESET
2812
MiMa RESET TIME 0..1439 min; Ø
2813
MiMa RESETCY-
CLE
2814
Min-
MaxRES.START
Waveform Capture
Addr.
Setting Title
402A
WAVEFORMTRIG-
GER
403A
WAVEFORM DATA Fault event
410
MAX. LENGTH
411
PRE. TRIG. TIME
412
POST REC. TIME
415
BinIn CAPT.TIME
7SA6 Manual
C53000-G1176-C133-1
Setting Options
15 Min per., 1 Sub
15 Min per., 3 Subs
15 Min per., 15 Subs
30 Min per., 1 Sub.
60 Min per., 1 Sub.
On the Hour
15 Min. after Hour
30 Min. after Hour
45 Min. after Hour
Setting Options
NO
YES
1..365 day(s)
1..365 Days
Setting Options
Save with Pickup
Save with TRIP
Start with TRIP
Power System fault
0.30..5.00 sec
0.05..0.50 sec
0.05..0.50 sec
0.10..5.00 sec; ∞
Default Setting
60 Min per., 1 Sub. Demand Calculation Intervals
On the Hour
Demand Synchronization Time
Default Setting
YES
Automatic Cyclic Reset Function
0 min
MinMax Reset Timer
7 day(s)
MinMax Reset Cycle Period
1 Days
MinMax Start Reset Cycle in
Default Setting
Save with Pickup
Waveform Capture
Fault event
Scope of Waveform Data
1.00 sec
Max. length of a Waveform Cap-
ture Record
0.10 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
Functions
Comments
Comments
Comments
6-289