Siemens siprotec 7SA6 User Manual page 420

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
Circuit Breaker
Pole Discrepancy
Supervision
6.16.2 Applying the Function Parameter Settings
General
Breaker Failure
Protection
6-238
The pole discrepancy supervision has the task to detect discrepancies in the position
of the three circuit breaker poles. Under steady-state conditions, either all three poles
of the breaker must be closed, or all three poles must be open. Discrepancy is
permitted only for a short time interval during a single-pole automatic reclose cycle.
The scheme functionality is shown in Figure 6-126. The signals which are processed
here are the same as those used for the breaker failure protection. The pole
discrepancy condition is established when at least one pole is closed ("CB any pole
closed") and at the same time not all poles are closed ("CB any pole open").
Additionally, the current criteria (from Figure 6-113) are processed. Pole discrepancy
can only be detected when current is not flowing through all three poles (<3), i.e.
through only one or two poles. When current is flowing through all three poles, all three
poles must be closed even if the breaker auxiliary contacts indicate a different status.
If pole discrepancy is detected, this is annunciated by a fault detection signal. This
signal identifies the pole which was open before the trip command of the pole
discrepancy supervision occurred.
L1>
L2>
L3>
CB any pole closed
CB any pole open
Figure 6-126 Function block diagram of pole discrepancy supervision
The breaker failure protection and its ancillary functions (end fault protection, pole
discrepancy supervision) can only operate if they were configured as HQDEOHG during
setting of the scope of functions (see Section 5.1, address ).
The complete breaker failure protection including its ancillary functions is switched Off
or On under address  )&7 %UHDNHU)DLO.
The current threshold ,! %) (address ) should be selected such that the
protection will operate with the smallest expected short-circuit current. To ensure this,
the value should be 10 % less than the minimum anticipated fault current. On the other
hand, the value should not be set lower than necessary.
&
&
&
<3
3932
&
FNo 1497
BF CBdiscr L1
FNo 1498
BF CBdiscr L2
FNo 1499
BF CBdiscr L3
T-PoleDiscrep.
FNo 1500
T
0
BF CBdiscr TRIP
C53000-G1176-C133-1
7SA6 Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents