Analog Outputs; Method Of Operation; Applying The Function Parameter Settings - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
6.18

Analog Outputs

6.18.1 Method of Operation

6.18.2 Applying the Function Parameter Settings

Measure Values
6-248
Depending on the ordering version the 7SA6 relay up to four analog outputs are
available. During the configuration of the functional scope (see Figure 5.1) it was
determined which values may be transmitted via these interfaces. Up to four outputs
can be selected out of the following list:
• Measured value I
(current of phase L2) in per cent of the operational nominal
L2
current
• Measured value U
L2–L3
operational nominal voltage
• Measured value |P| (value of active power) in per cent of the operational nominal
power √3·U
·I
N
N
• Measured value |Q| (value of reactive power) in per cent of the operational nominal
apparent power √3·U
• Fault distance d in per cent of line length on the basis of the configured reactance
per unit length and the line length (Address  to , see also Subsection
6.1.3)
• Fault distance d in kilometres or miles, depending on the configured length unit
(Address , see also Subsection 6.1.1), on the basis of the configured
reactance per unit length (Address  or , see also Subsection 6.1.3)
• Fault current I
, i. e. the maximum of 3 phase currents during clearance of the
max
last fault, primary in Ampere, on the basis of the configured primary and secondary
nominal current (Address  and , see also Subsection 6.1.1)
The operational nominal values are the nominal values configured according to
Address  and  (see also Subsection 6.1.3).
The analog values are output as current source. The nominal range of the analog
outputs is 0 mA to 20 mA, the operating range may reach up to 22.5 mA. The
conversion factor and the valid range can be set.
Once the measured values are selected (Section 5.1, Addresses  to ), set
the conversion factor and the valid range for the available outputs, as follows:
for analog output 1 at mounting location "B" (Port B1):
Address   P$ %
Address  0,1 9$/8( % the minimum value permitted
for analog output 2 at mounting location "B" (Port B2):
Address   P$ %
Address  0,1 9$/8( % the minimum value permitted
(phase-to-phase voltage L2-L3) in per cent of the
·I
N
N
value in % to be indicated at 20 mA
value in % to be indicated at 20 mA
7SA6 Manual
C53000-G1176-C133-1