Circuit Breaker Failure Protection; Method Of Operation - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.16

Circuit Breaker Failure Protection

6.16.1 Method of Operation

General
7SA6 Manual
C53000-G1176-C133-1
The circuit breaker failure protection provides rapid back-up fault clearance, in the
event that the circuit breaker fails to respond to a trip command from a feeder
protection.
Whenever e.g. a short-circuit protection relay of a feeder issues a trip command to the
circuit breaker, this is repeated to the breaker failure protection (Figure 6-111). A timer
T–BF in the breaker failure protection is started. The timer runs as long as a trip
command is present and current continues to flow through the breaker poles.
Protection
trip
Feeder protection
(internal or external)
Figure 6-111 Simplified function diagram of circuit breaker failure protection with current flow
monitoring
Normally, the breaker will open and interrupt the fault current. The current monitoring
stage quickly resets (typical 10 ms) and stops the timer T–BF.
If the trip command is not carried out (breaker failure case), current continues to flow
and the timer runs to its set limit. The breaker failure protection then issues a
command to trip the back-up breakers and interrupt the fault current.
The reset time of the feeder protection is not relevant because the breaker failure
protection itself recognizes the interruption of the current.
For protection functions where the tripping criteria is not dependent on current (e.g.
Buchholz protection), current flow is not a reliable criterion for proper operation of the
breaker. In such cases, the circuit breaker position can be derived from the auxiliary
contacts of the breaker. Therefore, instead of monitoring the current, the condition of
the auxiliary contacts is monitored (see Figure 6-112). For this purpose, the outputs
from the auxiliary contacts must be fed to binary inputs on the relay (refer also Section
6.20.2).
Circuit breaker failure protection
I> BF
Feeder
Functions
Bus-bar
T–BF
0
&
bus-bar
Trip
6-227

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents