Installation and Commissioning
Analog Output
Module
Replacing
Interface Modules
8-34
The RS 485 interface can be modified to a RS232 interface by rearranging the
jumpers.
The jumper settings for the alternative interfaces RS232 or RS485 (according to
Figure 8-18) are listed in Table 8-21.
Table 8-21
Configuration for RS232 or RS485 on the interface module according to Figure
8-18
Jumper
X5
X6
RS232
1–2
1–2
RS485
2–3
2–3
The jumpers X5 to X10 must be plugged in the same way!
Jumper presettings are in accordance with the ordered configuration.
The analog output module AN20 is provided with 2 isolated channels with a current
range from 0 to 20 mA (unipolar, maximum 350 Ω).
The mounting location on the processor circuit board C–CPU–2 is "B" and/or "D",
dependent on the version (see Figure 8-17).
AN20
SIEMENS
Figure 8-20
Interface module with the analog output AN20
The interface modules can be replaced. Refer to Figure 8-17 for physical arrangement
of the modules. The order numbers of the replacement module can be found in
Appendix A, Section A.1.1.
Please note the following:
q
Only interface modules of devices with panel flush mounting and cubicle mounting
as well as of mounting devices with detached operator panel can be exchanged.
Interface modules of devices in surface mounting housings with double-level
terminals must be exchanged in our manufacturing centre.
q
Use only interface modules that can be ordered in our facilities
(see also Appendix A, Section A.1.1).
X7
X8
X10
1–2
1–2
1–2
2–3
2–3
2–3
C53207-A322-
B140-1
X11
X12
X13
2–3
1–2
1–2
2–3
1–2
1–2