Siemens siprotec 7SA6 User Manual page 147

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

7SA6 Manual
C53000-G1176-C133-1
may also define the units for pulsed measured values (309) (Figure 5-20), the
conversion factor, and the number of decimal places (Figure 5-21). If ZLSLQJ
SXOVH6 is selected, each individual impulse increases the counter by one. If the
double current pulse option is selected, then each individual transition (positive or
negative) increases the counter by one. If, for example, MVARh is entered as the units
and 1000 is entered as the conversion factor, then 1000 impulses are equal to 1
MVARh.
Figure 5-20
Information Properties, Example for Information Type "Pulse Measured Value"
(PMV)
Configuration
5-23