Addr.
Setting Title
1602
DELAY FORW. PU Distance protec-
1603
DELAY NON-DIR
1610
Iph>>
1611
Iph>
1612
Uph-e (I>>)
1613
Uph-e (I>)
1614
Uph-ph (I>>)
1615
Uph-ph (I>)
1616
Iphi>
1617
Uph-e (Iphi>)
1618
Uph-ph (Iphi>)
EFFECT ϕ
1619A
ϕ >
1620
ϕ <
1621
1630A
1ph FAULTS
2002
P/S Op. mode
2006
PowerSwing trip
2101
FCT Telep. Dis.
2102
Type of Line
2103A
Send Prolong.
2107A
Delay for alarm
2108
Release Delay
7SA6 Manual
C53000-G1176-C133-1
Function
Setting Options
0.00..30.00 sec; ∞
tion, general set-
tings
0.00..30.00 sec; ∞
Distance protec-
tion, general set-
tings
Distance protec-
0.25..10.00 A
tion, general set-
tings
Distance protec-
0.10..4.00 A
tion, general set-
tings
Distance protec-
20..70 V
tion, general set-
tings
Distance protec-
20..70 V
tion, general set-
tings
Distance protec-
40..130 V
tion, general set-
tings
Distance protec-
40..130 V
tion, general set-
tings
Distance protec-
0.10..8.00 A
tion, general set-
tings
Distance protec-
20..70 V
tion, general set-
tings
Distance protec-
40..130 V
tion, general set-
tings
Distance protec-
forward and reverse
tion, general set-
Forward
tings
30..60 °
Distance protec-
tion, general set-
tings
90..120 °
Distance protec-
tion, general set-
tings
Distance protec-
phase-earth
tion, general set-
phase to phase only
tings
Power Swing
all zones blocked
Z1/Z1B blocked
Z2 to Z5 blocked
Z1,Z1B,Z2 blocked
Power Swing
NO
YES
Teleprotection for
ON
Distance prot.
OFF
Teleprotection for
Two Terminals
Distance prot.
Three Terminals
Teleprotection for
0.00..30.00 sec
Distance prot.
Teleprotection for
0.00..30.00 sec
Distance prot.
Teleprotection for
0.000..30.000 sec
Distance prot.
Default Setting
1.20 sec
Trip delay for Forward-PICKUP
1.20 sec
Trip delay for Reverse/Non-direc.
PICKUP
1.80 A
Iph>> Pickup (overcurrent)
0.20 A
Iph> Pickup (minimum current)
48 V
Undervoltage (ph-e) at Iph>>
48 V
Undervoltage (ph-e) at Iph>
80 V
Undervoltage (ph-ph) at Iph>>
80 V
Undervoltage (ph-ph) at Iph>
0.50 A
Iphi> Pickup (minimum current at phi>)
48 V
Undervoltage (ph-e) at Iphi>
80 V
Undervoltage (ph-ph) at Iphi>
forward and reverse
Effective direction of phi-pickup
50 °
PHI> pickup (lower setpoint)
110 °
PHI< pickup (upper setpoint)
phase-earth
1ph-pickup loop selection (PU w/o
earth)
all zones blocked
Power Swing Operating mode
NO
Power swing trip
ON
Teleprotection for Distance prot. is
Two Terminals
Type of Line
0.05 sec
Time for send signal prolongation
10.00 sec
Unblocking: Time Delay for Alarm
0.000 sec
Time Delay for release after pickup
Appendix
Comments
B-9

Hide quick links: