Checking The Connections; Data Connections - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Installation and Commissioning
8.2

Checking the Connections

8.2.1

Data Connections

PC Operating
Interface at Front
System (SCADA)
Interface
8-36
The following tables list the pin-assignments for the various serial interfaces of the
device and the time synchronization interface.
When the recommended communication cable is used, correct connection between
®
the SIPROTEC
device and the PC is automatically ensured. See the Appendix, Sub-
section for an ordering description of the cable.
When a serial interface of the device is connected to a central substation control
system, the data connection must be checked. A visual check of the transmit channel
and the receive channel is important. Each connection is dedicated to one
transmission direction. The data output of one device must be connected to the data
input of the other device, and vice versa.
The data cable connections are designated in sympathy with DIN 66020 and ISO
2110 (see also Table 8-23):
− TxD
data transmit
− RxD
data receive
− RTS
request to send
− CTS
clear to send
− DGND
signal/chassis ground
The cable shield is to be grounded at both ends so that potential differences cannot
cause circulating currents to flow along the shield.
The physical arrangement of the connectors is illustrated in Sub-section 2.1.5, Figure
2-19.
Table 8-23
Installation of the D-subminiature ports
Pin No.
Operating
interface
1
2
RxD
3
TxD
4
5
DGND
6
7
RTS
8
CTS
9
*) Pin 7 also may carry the RS232 RTS signal to an RS485 interface. Pin 7 must therefore
not be connected!
RS232
RS485
Shield (with shield ends electrically connected)
RxD
TxD
A/A' (RxD/TxD–N)
DGND
C/C' (DGND)
RTS
–*)
CTS
B/B' (RxD/TxD–P)
Profibus FMS Slave, RS485
B/B' (RxD/TxD–P)
CNTR–A (TTL)
C/C' (DGND)
+5 V (max. load 100 mA)
A/A' (RxD/TxD–N)
7SA6 Manual
C53000-G1176-C133-1