Siemens siprotec 7SA6 User Manual page 411

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Processing of the
Circuit Breaker
Auxiliary Contacts
7SA6 Manual
C53000-G1176-C133-1
I
L1
I
L2
I
L3
3I
2
3I
0
Figure 6-113 Current flow monitoring with the plausibility currents 3· I
The position of the circuit breaker is derived from the central function control of the
device (refer also to Section 6.20.2). Evaluation of the breaker auxiliary contacts is
carried out in the breaker failure protection function only when the current flow
monitoring has not picked up. Once the current flow criterion has picked up during the
trip signal from the feeder protection, the circuit breaker is assumed to be open as
soon as the current disappears, even if the associated auxiliary contact does not (yet)
indicate that the circuit breaker has opened (Figure 6-114). This gives preference to
the more reliable current criterion and avoids overfunctioning due to a defect e.g. in
the auxiliary contact mechanism or circuit. This interlock feature is provided for each
individual phase as well as for three-pole trip.
It is possible to disable the auxiliary contact criterion. If you set the parameter switch
&KN %5. &217$&7 (Figure 6-116 above) to 1R, the breaker failure protection can
only be started when current flow is detected. The position of the auxiliary contacts is
then not evaluated even if the auxiliary contacts are connected to the device.
"(! D3Ã7A
D3
D3
D3
D3
> 1
plausi-
bility
D3
Current
criterion
> 1
&
L1>
&
> 1
&
L2>
&
> 1
&
L3>
&
and 3·I
0
2
Functions
6-229