Siemens siprotec 7SA6 User Manual page 743

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
3731
U1>(>)
3732
U1>
3733
T U1>
3734
U1>>
3735
T U1>>
3739A
U1>(>) RESET
3741
U2>(>)
3742
U2>
3743
T U2>
3744
U2>>
3745
T U2>>
3749A
U2>(>) RESET
3751
Uph-e<(<)
3752
Uph-e<
3753
T Uph-e<
3754
Uph-e<<
3755
T Uph-e<<
3758
CURR.SUP. Uphe< Voltage Protection
3761
Uph-ph<(<)
3762
Uph-ph<
3763
T Uph-ph<
3764
Uph-ph<<
3765
T Uphph<<
3768
CURR.SUP.Uphph
<
3771
U1<(<)
3772
U1<
3773
T U1<
3774
U1<<
3775
T U1<<
3778
CURR.SUP.U1<
3802
START
3805
Paral.Line Comp
3806
Load Compensat.
3811
Tmax OUTPUT
BCD
7SA6 Manual
C53000-G1176-C133-1
Function
Setting Options
Voltage Protection
OFF
Alarm Only
ON
Voltage Protection
2.0..220.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
2.0..220.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
0.50..0.98
Voltage Protection
OFF
Alarm Only
ON
Voltage Protection
2.0..220.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
2.0..220.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
0.50..0.98
Voltage Protection
OFF
Alarm Only
ON
Voltage Protection
1.0..100.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
1.0..100.0 V
0.00..30.00 sec; ∞
Voltage Protection
ON
OFF
Voltage Protection
OFF
Alarm Only
ON
Voltage Protection
1.0..175.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
1.0..175.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
ON
OFF
Voltage Protection
OFF
Alarm Only
ON
Voltage Protection
1.0..100.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
1.0..100.0 V
0.00..30.00 sec; ∞
Voltage Protection
Voltage Protection
ON
OFF
Fault Locator
Pickup
TRIP
Fault Locator
NO
YES
Fault Locator
NO
YES
Fault Locator
0.10..30.00 sec
Default Setting
OFF
Operating mode U1 overvoltage prot.
150.0 V
U1> Pickup
2.00 sec
T U1> Time Delay
175.0 V
U1>> Pickup
1.00 sec
T U1>> Time Delay
0.98
U1>(>) Reset ratio
OFF
Operating mode U2 overvoltage prot.
30.0 V
U2> Pickup
2.00 sec
T U2> Time Delay
50.0 V
U2>> Pickup
1.00 sec
T U2>> Time Delay
0.98
U2>(>) Reset ratio
OFF
Operating mode Uph-e undervoltage
prot.
30.0 V
Uph-e< Pickup
2.00 sec
T Uph-e< Time Delay
10.0 V
Uph-e<< Pickup
1.00 sec
T Uph-e<< Time Delay
ON
Current supervision (Uph-e)
OFF
Operating mode Uph-ph undervoltage
prot.
50.0 V
Uph-ph< Pickup
2.00 sec
T Uph-ph< Time Delay
17.0 V
Uph-ph<< Pickup
1.00 sec
T Uph-ph<< Time Delay
ON
Current supervision (Uph-ph)
OFF
Operating mode U1 undervoltage prot.
30.0 V
U1< Pickup
2.00 sec
T U1< Time Delay
10.0 V
U1<< Pickup
1.00 sec
T U1<< Time Delay
ON
Current supervision (U1)
Pickup
Start fault locator with
NO
Mutual coupling parall.line compensa-
tion
NO
Load Compensation
0.30 sec
Maximum output time via BCD
Appendix
Comments