Settings - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
6.2.2.5

Settings

Addr.
Setting Title
1601
PROGAM U/I
1602
DELAY FORW. PU
1603
DELAY NON-DIR.
1630A
1ph FAULTS
1610
Iph>>
1611
Iph>
1612
Uph-e (I>>)
1613
Uph-e (I>)
1614
Uph-ph (I>>)
1615
Uph-ph (I>)
1616
Iphi>
1617
Uph-e (Iphi>)
1618
Uph-ph (Iphi>)
EFFECT ϕ
1619A
ϕ >
1620
ϕ <
1621
6-40
Note: The indicated secondary current values and values of impedance for setting
ranges and default settings refer to I
values are to be multiplied by 5. The values of impedance are divided by 5.
Function
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
Distance protection, general
settings
= 1 A. For the nominal current 5 A the current
N
Setting Options
Ph-E: Uphe/ Ph-Ph:
Ph-E: Uphe/ Ph-Ph: Uphph
Uphph
Ph-E: Uphph/Ph-Ph:
Uphph
Ph-E: Uphe/Ph-Ph:
Uphe
Ph-E: Uphe/Ph-Ph: I>>
0.00..30.00 sec; ∞
1.20 sec
0.00..30.00 sec; ∞
1.20 sec
phase-earth
phase-earth
phase to phase only
0.25..10.00 A
1.80 A
0.10..4.00 A
0.20 A
20..70 V
48 V
20..70 V
48 V
40..130 V
80 V
40..130 V
80 V
0.10..8.00 A
0.50 A
20..70 V
48 V
40..130 V
80 V
forward and reverse
forward and reverse
Forward
30..60 °
50 °
90..120 °
110 °
Default Setting
7SA6 Manual
C53000-G1176-C133-1