Siemens siprotec 7SA6 User Manual page 136

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Configuration
Information
5-12
described in general in Chapter 4. Details regarding the settings for various functions
are found in Chapter 6.
The settings group to be processed may be selected via the menu item 9LHZ →
6HWWLQJ *URXS.
The column header ,QIRUPDWLRQ contains the function number, the LCD text
(display text), an explanation (long text), and the information type. The following
abbreviations are used for the information types:
• Annunciations:
− SP
Single Point Indication (binary input, e.g. LED reset, refer also to
subsection 5.2.1)
− DP
Double Point Indication (binary input, refer also to subsection 5.2.1)
− OUT
Output Indication (protection output signals e.g. pickup, trip ...)
− IntSP
Internal Single Point Indication,
− IntDP
Internal Double Point Indication.
− TxTap
Transformer Tap Indication
• Control Commands for switching devices (refer to subsection 5.2.3):
− C_S
Single Command with Single Output without Feedback,
− CF_S
Single Command with Single Output with Feedback,
− C_SN
Single Command with Single Output Negated without Feedback,
− C_D2
Double Command (2 relays) with Single Outputs without Feedback,
− CF_D2
Double Command (2 relays) with Single Outputs with Feedback,
− C_D12
Double Command with Single Trip Outputs and Double Close Outputs
without Feedback,
− CF_D12 Double Command with Single Trip Outputs and Double Close Outputs
with Feedback,
− C_D3
Double Command (3 relays) with Single Outputs and Common Output
without Feedback,
− CF_D3
Double Command (3 relays) with Single Outputs and Common Output
with Feedback,
− C_D4
Double Command (4 relays) with Double Outputs without Feedback,
− CF_D4
Double Command (4 relays) with Double Outputs with Feedback,
− C_D2N
Double Command (2 relays) with Single Outputs Negated
without Feedback,
− CF_D2N Double Command (2 relays) with Single Outputs Negated with
Feedback.
• Measured Values:
− MV
Measured Value,
− MVU
Measured Value, User Defined,
− MVT
Measured Value with Time,
− LV
Limit Value,
− LVU
Limit Value, User Defined.
• Metered Values:
− MVMV
Metered Value of Measured Value,
− PMV
Pulse Measured Value.
The information contains various properties depending on the information type, which
are partially fixed and may be partially influenced.
7SA6 Manual