Settings; Information Overview - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.15.3 Settings

Addr.
Setting Title
3802
START
3805
Paral.Line Comp
3806
Load Compensat.
3811
Tmax OUTPUT
BCD

6.15.4 Information Overview

F.No.
Alarm
1114
Rpri =
1115
Xpri =
1117
Rsec =
1118
Xsec =
1119
dist =
1120
d[%] =
1122
dist =
1123
FL Loop L1E
1124
FL Loop L2E
1125
FL Loop L3E
1126
FL Loop L1L2
1127
FL Loop L2L3
1128
FL Loop L3L1
1132
Flt.Loc.invalid
1133
Flt.Loc.ErrorK0
1143
BCD d[1%]
1144
BCD d[2%]
1145
BCD d[4%]
1146
BCD d[8%]
1147
BCD d[10%]
1148
BCD d[20%]
1149
BCD d[40%]
1150
BCD d[80%]
1151
BCD d[100%]
7SA6 Manual
C53000-G1176-C133-1
Setting Options
Pickup
TRIP
NO
YES
NO
YES
0.10..30.00 sec
Flt Locator: primary RESISTANCE
Flt Locator: primary REACTANCE
Flt Locator: secondary RESISTANCE
Flt Locator: secondary REACTANCE
Flt Locator: Distance to fault
Flt Locator: Distance [%] to fault
Flt Locator: Distance to fault
Fault Locator Loop L1E
Fault Locator Loop L2E
Fault Locator Loop L3E
Fault Locator Loop L1L2
Fault Locator Loop L2L3
Fault Locator Loop L3L1
Fault location invalid
Fault locator setting error K0,angle(K0)
BCD Fault location [1%]
BCD Fault location [2%]
BCD Fault location [4%]
BCD Fault location [8%]
BCD Fault location [10%]
BCD Fault location [20%]
BCD Fault location [40%]
BCD Fault location [80%]
BCD Fault location [100%]
Default Setting
Pickup
Start fault locator with
NO
Mutual coupling parall.line com-
pensation
NO
Load Compensation
0.30 sec
Maximum output time via BCD
Comments
Functions
Comments
6-225

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents