Reverse Interlocking - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
6.4.1.9

Reverse Interlocking

6-94
If the distance protection 7SA6 is used as back-up protection in single-end fed
transformer feeders, the reverse interlocking function ensures a fast protection of the
busbar without endangering the selectivity for faults on the outgoing feeders.
According to Figure 6-57 the distance zones Z1 and Z2 serve as back-up stages for
faults on the outgoing lines, for example a fault in F2. For distance grading the shortest
outgoing line is to be used.
The overreach zone Z1B, whose delay time T1B must be set longer than the pickup
time Ta of the protection devices of the outgoing lines, is blocked after the pickup of
an inferior protection. The pickup signal is sent (according to Figure 6-57) via the
receive input of the distance protection.
If no signal is received this zone guarantees fast tripping of the busbar for
- faults on the busbar, such as for example in F1,
- failure of the line protection during a fault, such as for example in F2.
The reverse interlocking of the distance protection is performed by specific release or
blocking of the overreach zone Z1B. It can be realized by the blocking mode (see
Figure 6-57) or the release mode.
To avoid transient false signals after clearance of external faults, the blocking
condition of the reverse interlocking is extended by a transient blocking time (TB in
Figure 6-57).
7SA6
Z1B
T1B
&
.
Direc
Tripping
0
TB
Figure 6-57
Reverse interlocking — functional principle and grading example
Pickup
L+
Pick.
L+
F1
.
Pick
L+
.
Pick
L+
T2
Z1
T1
Z1B
T1B
Ta
Shortest Line
F2
7SA6 Manual
C53000-G1176-C133-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents