Appendix
Addr.
Setting Title
3147
Add.T-DELAY
3148
3I0p Telep/BI
3149
3I0p SOTF-Trip
3150
3I0p InrushBlk
3151
IEC Curve
3152
ANSI Curve
3153
LOG Curve
3154
3I0p Startpoint
3160
POLARIZATION
3162A
Dir. ALPHA
3163A
Dir. BETA
3164
3U0>
3165
IY>
3166
3U2>
3167
3I2>
3170
2nd InrushRest
3171
Imax InrushRest
3172
SOTF Op. Mode
3173
SOTF Time DELAY Earth fault overcur-
3182
3U0>(U0 inv)
3183
U0inv. minimum
3184
T forw. (U0inv)
3185
T rev. (U0inv)
3201
FCT Telep. E/F
B-14
Function
Setting Options
0.00..30.00 sec; ∞
Earth fault overcur-
rent
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
Normal Inverse
rent
Very Inverse
Extremely Inverse
Long time inverse
Earth fault overcur-
Inverse
rent
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Earth fault overcur-
Logarithmic inverse
rent
Earth fault overcur-
1.0..4.0
rent
Earth fault overcur-
with U0 and IY (dual polar-
rent
ized)
with IY (transformer star
point current)
with U2 and I2 (negative
sequence)
0..360 °
Earth fault overcur-
rent
0..360 °
Earth fault overcur-
rent
Earth fault overcur-
0.5..10.0 V
rent
Earth fault overcur-
0.05..1.00 A
rent
Earth fault overcur-
0.5..10.0 V
rent
Earth fault overcur-
0.05..1.00 A
rent
Earth fault overcur-
10..45 %
rent
Earth fault overcur-
0.50..25.00 A
rent
Earth fault overcur-
with Pickup (non-directional)
rent
with Pickup and direction
0.00..30.00 sec
rent
Earth fault overcur-
1.0..10.0 V
rent
Earth fault overcur-
0.1..5.0 V
rent
Earth fault overcur-
0.00..32.00 sec
rent
Earth fault overcur-
0.00..32.00 sec
rent
Teleprotection for
ON
Earth fault overcurr.
OFF
Default Setting
1.20 sec
Additional Time Delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
NO
Inrush Blocking
Normal Inverse
IEC Curve
Inverse
ANSI Curve
Logarithmic inverse
LOGARITHMIC Curve
1.1
Start point of inverse characteristic
with U0 and IY (dual polar-
Polarization
ized)
338 °
ALPHA, lower angle for forward direc-
tion
122 °
BETA, upper angle for forward direc-
tion
0.5 V
Min. zero seq.voltage 3U0 for polariz-
ing
0.05 A
Min. earth current IY for polarizing
0.5 V
Min. neg. seq. polarizing voltage 3U2
0.05 A
Min. neg. seq. polarizing current 3I2
15 %
2nd harmonic ratio for inrush restraint
7.50 A
Max.Current, overriding inrush
restraint
with Pickup and direction
Instantaneous mode after Switch-
OnToFault
0.00 sec
Trip time delay after SOTF
5.0 V
3U0> setpoint
0.2 V
Minimum voltage U0min for T->oo
0.90 sec
T-forward Time delay (U0inv)
1.20 sec
T-reverse Time delay (U0inv)
ON
Teleprotection for Earth Fault O/C
Comments