Control During Operation
:
From PC with
®
DIGSI
4
7-48
To perform control, confirm with the
VXUH"". If the response is "<(6", the switching operation is initiated (provided the
Local command is allowed). A message is displayed and recorded indicating the
results of the control action. Acknowledge this by pressing the
The command is not executed if the switching operation is restricted. The operation
may be restricted for reasons pertaining to, for example, switching authority (see Sub-
section 7.4.6) or interlocking (see Sub-section 7.4.7). A message is displayed and
recorded indicating the results of the control action. Acknowledge the message by
pressing the
key. Parameters to set control properties can be examined in the
ENTER
display. Refer to Sub-section 7.4.4.
key can be used to return to %5($.(56:,7&+. Press the
The
to the 0$,1 0(18.
When the 2QOLQH window in DIGSI
functions for the device appear in the left part of the window. Clicking on &RQWURO
displays the associated function selection in the data window. See Figure 7-48.
Figure 7-48
Window for Control of Operating Resources in DIGSI
By double clicking on %UHDNHU6ZLWFKHV, a dialog field is opened in which the
present status of each switch is visible. See Figure 7-49. Control can be performed
from this dialog box provided the switching authority is set to 5(027(.
The switching authority is first transferred to DIGSI
window shown in Figure 7-49 is opened. The configuration matrix discussed in Section
5.2 determines the control devices that have information displayed in this field.
key. A safety inquiry appears, "$UH \RX
ENTER
®
4 is opened with a double click, the operating
®
4 at the moment the control
key once again.
ENTER
key to return
MENU
®
4 - (example)
7SA6 Manual
C53000-G1176-C133-1