Siemens siprotec 7SA6 User Manual page 206

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
6.1.3.1
Settings
Addr.
Setting Title
1103
FullScaleVolt.
1104
FullScaleCurr.
1105
Line Angle
1110
x'
1111
Line Length
1112
x'
1113
Line Length
1116
RE/RL(Z1)
1117
XE/XL(Z1)
1118
RE/RL(Z1B...Z5)
1119
XE/XL(Z1B...Z5)
1120
K0 (Z1)
1121
Angle K0(Z1)
1122
K0 (> Z1)
1123
AngleI K0(> Z1)
6-24
~
Multiple fault on a double-circuit line next to a generato
Figure 6-14
Address $ 7ULSSK)OW determines that the short-circuit protection functions
perform only a single-pole trip in case of isolated two-phase faults (clear of ground),
provided that single-pole tripping is possible and permitted. This allows a single-pole
rapid automatic reclosure cycle for this kind of fault. The trip type can be set to SROH
OHDGLQJ SKDVH or SROH ODJJLQJ SKDVH. The parameter is only available in
versions with single-pole tripping. This setting can only be changed with DIGSI
under "Additional Settings". If this option is used, it must be born in mind that the
phase preference should be the same throughout the entire network and that it must
be the same at all ends of one line. More information on the function is also contained
in Section 6.20.3 Overall Fault Detection Logic of the Device. The default setting is
WULSOHSROH.
Note: The indicated secondary current values and values of impedance for setting
ranges and default settings refer to I
values are to be multiplied by 5. The values of impedance are divided by 5.
Function
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
Power System Data 2
L1–E
L2–E
= 1 A. For the nominal current 5 A the current
N
Setting Options
1.0..1200.0 kV
10..5000 A
30..89 °
0.005..6.500 Ohm / km
1.0..1000.0 km
0.005..10.000 Ohm / mile 0.242 Ohm / mile
0.6..650.0 Miles
-.33..7.00
-.33..7.00
-.33..7.00
-.33..7.00
0.000..4.000
-135.00..135.00 °
0.000..4.000
-135.00..135.00 °
r
®
4
Default Setting
400.0 kV
1000 A
85 °
0.150 Ohm / km
100.0 km
62.1 Miles
1.00
1.00
1.00
1.00
1.000
0.00 °
1.000
0.00 °
7SA6 Manual
C53000-G1176-C133-1