Settings - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.2.3.3

Settings

Addr.
Setting Title
1201
FCT Distance
1202
Minimum Iph>
1215
Paral.Line Comp
1232
SOTF zone
1241
R load (Ø-E)
ϕ load (Ø-E)
1242
1243
R load (Ø-Ø)
ϕ load (Ø-Ø)
1244
1203
3I0> Threshold
1204
3U0> Threshold
1205
3U0> COMP/
ISOL.
1206
T3I0 1PHAS
1207A 3I0>/ Iphmax
1220
PHASE
PREF.2phe
1221A 2Ph-E faults
7SA6 Manual
C53000-G1176-C133-1
Note: The indicated secondary current values and values of impedance for setting
ranges and default settings refer to I
values are to be multiplied by 5. The values of impedance are divided by 5.
Function
Distance protection, general settings ON
Distance protection, general settings 0.10..4.00 A
Distance protection, general settings NO
Distance protection, general settings with Pickup (non-
Distance protection, general settings 0.10..250.00 Ohm;
Distance protection, general settings 20..60 °
Distance protection, general settings 0.10..250.00 Ohm;
Distance protection, general settings 20..60 °
Distance protection, general settings 0.05..4.00 A
Distance protection, general settings 1..100 V; ∞
Distance protection, general settings 10..200 V
Distance protection, general settings 0.00..0.50 sec
Distance protection, general settings 0.05..0.30
Distance protection, general settings L3 (L1) acyclic
Distance protection, general settings block leading ph-e
= 1 A. For the nominal current 5 A the current
N
Setting Options
ON
OFF
0.10 A
NO
YES
Inactive
directional)
with Zone Z1B
Inactive
∞ Ohm
45 °
∞ Ohm
45 °
0.10 A
5 V
40 V
0.04 sec
0.10
L3 (L1) acyclic
L1 (L3) acyclic
L2 (L1) acyclic
L1 (L2) acyclic
L3 (L2) acyclic
L2 (L3) acyclic
L3 (L1) cyclic
L1 (L3) cyclic
all loops
block leading ph-e loop
loop
block lagging ph-e
loop
all loops
only phase-phase
loops
only phase-earth
loops
Functions
Default Setting
6-51