Section 5: Supervision Functions; Circuit Breaker Failure (50Bf); Figure 5.1-1 Logic Diagram: Circuit Breaker Fail Protection (50Bf) - Siemens 7SR224 Description & Operation

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

(1) Description of Operation 7SR224

Section 5: Supervision Functions

5.1
C
B
IRCUIT
REAKER
The circuit breaker fail function has two time delayed outputs that can be used for combinations of re-
tripping or back-tripping. CB Fail outputs are given after elapse of the 50BF-1 Delay or 50BF-2 Delay
settings.
The circuit breaker fail protection time delays are initiated either from:
An output Trip Contact of the relay (MENU: OUTPUT CONFIG\BINARY OUTPUT
CONFIG\Trip Contacts), or
A binary input configured 50BF Ext Trip (MENU: INPUT CONFIG\BINARY INPUT
MATRIX\50BF Ext Trip).
A binary or virtual input assigned to 50BF Mech Trip (MENU: INPUT CONFIG\INPUT
MATRIX\ 50BF Mech Trip).
CB Fail outputs will be issued providing any of the 3 phase currents are above the 50BF Setting or
the current in the fourth CT is above 50BF-I4 for longer than the 50BF-n Delay setting, or for a
mechanical protection trip the circuit breaker is still closed when the 50BF-n Delay setting has expired
– indicating that the fault has not been cleared.
Both 50BF-1 and 50BF-2 can be mapped to any output contact or LED.
If the 50BF CB Faulty input (MENU: INPUT CONFIG\INPUT MATRIX\50BF CB Faulty) is energised
when a CB trip is given the time delays 50BF-n Delay will be by-passed and the output given
immediately.
Operation of the CB Fail elements can be inhibited from:
Inhibit 50BF
Figure 5.1-1
Page 52 of 66
F
(50BF)
AILURE
A binary or virtual input.
Logic Diagram: Circuit Breaker Fail Protection (50BF)
©2009 Siemens Protection Devices Limited

Advertisement

Table of Contents
loading

Table of Contents