CHAPTER 6 - DETAILED PARAMETER DESCRIPTION

6.2 REGULATION PARAMETERS - P100 to P199

[Factory Setting]
Parameter
P100
Acceleration Time
0.1 s (< 99.9) -1 s (> 99.9)
P101
Deceleration Time
0.1 s (< 99.9) -1 s (> 99.9)
P102
Acceleration Time 2
0.1 s (< 99.9) - 1 s (> 99.9)
P103
Deceleration Time 2
0.1 s (< 99.9) - 1 s (> 99.9)
P104
S Ramp
P120
Speed Reference
Backup
124
Range
Unit
Description / Notes
0.0 to 999
Setting the value to 0.0 s results in no Acceleration ramp.
[ 20 ]
Defines the time to accelerate (P100) linearly from zero up to the
maximum speed (P134) or to decelerate (P101) linearly from the
maximum speed down to 0 rpm.
0.0 to 999
The selection of the acceleration / deceleration time ramp 2 (P102 or
[ 20 ]
P103) can be made by reprogramming one of the digital inputs DI3 to
DI8. Refer to P265 to P270 in ramp 2.
0.0 to 999
[ 20 ]
0.0 to 999
[ 20 ]
0 to 2
[ 0 ]
-
The ramp S reduces the mechanical stress during the acceleration and
deceleration of the load.
0 or 1
Defines if the Frequency Reference Backup function is disabled (0) or
[ 1 ]
enabled (1).
-
If P120 = Off, the inverter does not save the current reference value,
when the inverter is enabled again, it will restart from the minimum
frequency setting (P133).
This back-up function is applicable to the keypad (HMI), E.P., Serial,
Fieldbus and PID Setpoint (P525) references.
P104
0
1
2
Table 6.1 - Choosing S or linear ramp
Speed
Linear
50 % S ramp
100 % S ramp
Accel. Time
(P100/102)
Figure 6.1 - S or linear ramp
S Ramp
Inactive
50 %
100 %
Time
Decel. Time
(P101/103)