CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
P027
Analog Output AO1
P028
Analog Output AO2
P029
Analog Output AO3
P030
Analog Output AO4
P040
PID Process Variable
P042
Powered Time
LED: 0 to 6553h (x10)
P043
Enabled Time
122
Range
Unit
Description / Notes
Indicate the percentage value of the analog outputs AO1 to AO4 with
0.0 to 100
respect to the full-scale value. The indicated values are obtained after
[ - ]
the multiplication by the gain. Refer to the description of parameters
0.1 %
P251 to P258.
0.0 to 100
[ - ]
0.1 %
-100 to +100
[ - ]
0.1 %
-100 to +100
[ - ]
0.1 %
It indicates the process variable in % (factory setting), used as the PID
0 to 100
Feedback.
[ - ]
%
The indication unit can be changed through P530, P531 and P532. The
scale can be changed through P528 and P529.
Refer to detailed description in item 6.5 - Special Function Parameters.
This parameter also allows to modify the PID set point (see P525), when
P221 = 0 or P222 = 0.
Indicates the total number of hours that the inverter was powered.
LCD: 0 to 65535
The LED Display shows the total number of hours that the inverter was
[ - ]
energized divided by 10.
1 h
This value remains stored even when the inverter is turned OFF.
Example: Indication of 22 hours powered.
Indicates the total number of hours that the inverter has run.
0 to 6553.5
[ - ]
Indicates up to 6553.5 hours, rolls over to 0000.
0.1 h (< 999.9)
If P204 is set to 3, the P043 is reset to zero.
1 h (> 1000)
This value remains stored even when inverter is turned OFF.
Hours Energized
P042 = 22 h