CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES

8.12.4 DeviceNet

284
NOTE!
The parameters P000, P001, P215 and P408 are not available for access
via network.
In order to be able to use the Profibus DP-V1 interface, one must select
the option 1, 2 or 3 at P309. This programming is the same for the Profibus
DP-V0 or DP-V1 interfaces.
A specific GSD file for this interface is supplied with the Profibus DP-V1
communication kit.
Introduction
The DeviceNet communication is used for industrial automation, mainly for
the control of valves, sensors, input/output units and automation equipment.
The DeviceNet communication Link is based on a communication protocol
"broadcast oriented", the Controller Area Network (CAN). The connection to
the DeviceNet network is realized by means of a shielded cable comprising a
twisted pair and two wires for the external power supply. The baud rate can be
set to 125 kbits/s, 250 kbits/s or 500 kbits/s. Figure 8.41 gives a general view
of a DeviceNet network.
Controller
Other
Devices
Device
Input/Output
Configuration
Fieldbus connector of user of the inverter
- Connector: 5 ways-connector of type plug-in with screwed terminal
(screw terminal).
- Pin:
Table 8.18 - Connection of the pins to the DeviceNet
DeviceNet
Sensor
Motor
Starter
Devices
Motor
Controller
Inverter
Figure 8.41 - DeviceNet network
Description
Pin
V-
1
CAN_L
2
Shield
3
CAN_H
4
V+