WEG CFW-09 User Manual page 251

Frequency inverter
Hide thumbs Also See for CFW-09:
Table of Contents

Advertisement

CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
PTC
R L
500
R L
500
rpm
A
252
Terminal XC5
Factory Default Function
1
NC
Not Connected
Motor Thermistor Input 1 - PTC1
2
DI8
(P270 = 16 refer to figure 6.33). As DI
normal refer to P270 figure 6.34.
Motor Thermistor Input 2 - PTC2
3
DGND (DI8)
(P270 = 16 refer to figure 6.33). As DI
normal refer to P270 figure 6.34.
4
DGND
0 V reference of the 24 Vdc source
Transistor Output 1: Not used
5
DO1
Commom point for Digital Input DI7
6
COMMOM
and Digital Outputs DO1 and DO2
Transistor Output 2: Not Used
7
DO2
Power Supply for the digital inputs/
8
24 Vdc
outputs
Isolated digital input: Not Used
9
DI7
10
SREF
Reference for RS-485
11
A-LINE
RS-485 A-LINE (-)
12
B-LINE
RS-485 B-LINE (+)
Analog Input 3: Frequency Reference
13
AI3 +
Program P221 = 3 or P222 = 3
14
AI3 -
0 V Reference for Analog Speed
15
AGND
I
Analog Output 1: Speed
I
16
AO1
0 V Reference for analog Output
17
AGND
I
Analog Output 2 : Motor Current
18
AO2
I
Avaliable to be connected to an external
power supply to energise the encoder
19
+ V
repeater output (XC8)
0 V reference of the external power supply
20
COM 1
Figure 8.4 - XC5 terminal block description (complete EBB board)
ATTENTION!
The isolation of the analog input AI3 and the analog outputs AO1
designed only to interrupt the ground loops. Do not connect these inputs to
high potentials.
ENCODER CONNECTION: Refer to item 8.2.
INSTALLATION
The EBB board is installed on the CC9 control board, secured with spacers
and connected via Terminal blocks XC11 (24 V) and XC3.
NOTE!
For the CFW-09 Size 1 Models (6 A, 7 A, 10 A and 13 A / 220-230 V and 3.6 A,
4 A, 5.5 A and 9 A / 380-480 V) the plastic cover must be removed to install the
EBB board.
Specifications
Actuation: 3.9 k Release:1.6 k
Min: resistance: 100 
Referenced to DGND* through a 249 
resistor
Grounded via a 249  resistor
Isolated, open collector, 24 Vdc, 50 mA
Max. required board (RL)  500 
Isolated, open collector, 24 Vdc, 50 mA
Max. required board (RL)  500 
24 Vdc ± 8 %. Isolated,
Capacity: 90 mA
Min. high level: 18 Vdc
Max. low level: 3 Vdc
Max. Voltage: 30 Vdc
Input Current.: 11 mA @ 24 Vdc
Isolated RS-485 serial port
Isolated analog input programmable on
P243: (0 to 10) V or (0 to 20) mA/(4 to
20) mA lin.: 10 bits (0.1 % of full scale
range) Impedance: 400 k (0 to 10) V
500  [(0 to 20) mA/(4 to 20) mA]
Isolated analog Outputs signals:
(0 to 20) mA / (4 to 20) mA
Scales: refer to P251 and P253
lin.: 11 bits (0.5 % of full scale range)
Required board (RL)  600 
External power supply: 5 V to 15 V,
consumption: 100 mA @ 5 V
Outputs not included.
I
and AO2
I
is

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF