II. Fault Messages
Parameters that
Parameters that are affected
affect others
and modified automatically
when set
P203
P223, P225, P226, P228, P237,
P265
P295
P156, P157, P158, P169 (V/F),
P290, P365, P366, P367
P151, P153, P321, P322, P323
P296
P400
P320
P214
P156, P157, P158
P401
P297
P402
P122, P123, P124, P125, P126,
P127, P128, P129, P130, P131,
P133, P134, P135, P208, P288,
P289
P403
P369, P402
P404
P399, P407
P406
P156, P157, P158
Table 1 - Interdependence among parameters: parameters that change the settings of
others when modified versus parameters that are automatically modified as a function of a
parameter setting (during start-up and/or normal operation)
Display
E00
Output Overcurrent/Short-Circuit
E01
DC Link Overvoltage
E02
DC Link Undervoltage
E03
Power Supply Undervoltage/Phase Loss
E04
(*)
Inverter Overtemperature/Pre-charge Circuit
Failure
E05
Output Overload (I x t Function)
E06
External Fault
Encoder Fault
E07
Valid for P202 = 4 (Vector with Encoder)
E08
CPU Error (watchdog)
E09
Program Memory Error
E10
Error in the Copy Function
E11
Output Ground Fault
E12
Dynamic Braking Resistor Overload
Motor or Encoder with Inverted Wires
E13
(Self-Tuning) (Valid for P202 = 4)
E15
Motor Phase Loss
E17
Overspeed Fault
E24
Programming Error
E28 to E30
Serial communication error
E31
Keypad Connection Fault
E32
Motor Overtemperature
E33
Speed without control
E34
Long period at torque limitation
E41
Self-Diagnosis Fault
E70
Internal DC Supply Undervoltage
E71
PLC Watchdog Error
(*) E04 can be "Pre-charge Circuit Failure" only in the following models:
 86 A/380-480 V,  70 A/220-230 V,  44 A/500-600 V and for all 500-690 V and
660-690 V models. E04 can also occur when signal with inverted polarity is applied
at analog inputs AI1/AI2. The E04 fault message can also occur in the models up to
130 A/ 200-230 V, 142 A/380-480 V and 63 A/500-600 V when the temperature at
the heatsink is lower than -10 ºC.
CFW-09 - QUICK PARAMETER REFERENCE
Condition where it occurs
During the
oriented
start-up
NO
NO
YES
YES
NO
YES
YES
YES
YES
YES
YES
Description
During
normal
operation
YES
YES
YES
NO
YES
NO
NO
YES
NO
YES
NO
Page
228
228
228
229
229
229
229
229
229
229
229
229
230
230
230
230
230
230
230
230
230
230
230
231
231
33