CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
P300
DC Braking Time
This parameter
is shown on the
display(s) only when
P202 = 0, 1, 2, 3 or 5
196
Range
Unit
Description / Notes
The option 1.25 kHz is not valid for the Vector Control (P202 = 3 or 4).
The option 10 kHz is not valid for the Sensorless Vector Control (P202 = 3)
and for the models with supply voltage between 500 V and 690 V (2.9 A to
79 A/500-600 V, 107 A to 472 A/500-690 V and 100 A to 428 A/660-690 V).
0.0 to 15.0
The DC braking feature provides a motor fast stop through the injection of
[ 0.0 ]
DC current.
0.1 s
This parameter sets the DC Braking Time when the inverter is operating
in the V/F, VVW or Sensorless Vector Control modes.
Figure 6.40 shows the operation of the DC Braking with a ramp to stop
(stop command). Refer to P301:
a) V/F Control
b) VVW and Sensorless Control
Control Mode
DC Braking at Start
V/Hz
VVW
P302 and P371
Vector Sensorless
P371 and P372
Table 6.48 - Parameters related to the DC braking
Motor
Speed
P301
+24 V
Start/ Stop - DIx
Motor
Speed
P301
+24 V
Start/ Stop - DIx
Figure 6.40 a) and b) - DC braking operation with a ramp to stop
DC Braking at Stop
-
P300, P301 and P302
P300, P301 and P302
P300, P301 and P372
P300
Time
Dead
Time
Open
P300
Time
Open