CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
address 0 (zero) on and the control bits are made available from address
100 on.
Table below shows the addressing of bits, parameters and basic variables:
Parameter Number
P000
P001
P100
Number of the
Basic Variable
V00
V01
V08
Bit Number
Bit 0
Bit 1
Bit 7
Bit Number
Bit 100
Bit 101
Bit 107
Note: All registers (parameters and basic variables) are considered as
holding type registers, referenced from 40000 or 4x, whilst the bits are
referenced from 0000 or 0x.
The status bits have the same functions of the bits 8 to 15 of the logic
status (basic variable 2). These bits are available only for read, thus any
attempt to write command returns error status to the master.
Parameters
Modbus Address
Decimal
Hexadecimal
0
1
100
Basic Variables
Modbus Address
Decimal
Hexadecimal
5000
1388h
5001
1389h
5008
1390h
Status Bits
Modbus Address
Decimal
Hexadecimal
00
00h
01
01h
07
07h
Commands Bits
Modbus Address
Decimal
Hexadecimal
100
64h
101
65h
107
6Bh
00h
01h
64h
319