[Factory Setting]
Parameter
P004
DC Link Voltage
P005
Motor Frequency
P006
rdy, run, Sub, Exy
Inverter Status
P007
Output Voltage
P009
Motor Torque
P010
Output Power
P012
Digital Inputs
LED = 0 to 255
DI1 to DI8 Status
Range
Unit
Description / Notes
0.0 to 1235
Indicates the inverter DC Link voltage in volt (V).
[ - ]
1 V
0.0 to 1020
Indicates the inverter output frequency in hertz (Hz).
[ - ]
0.1 Hz
Indicates the inverter status:
[ - ]
rdy- inverter is ready to be started or enabled;
-
run- inverter is enabled;
Sub- inverter is disabled and line voltage is too low for operation
(undervoltage);
Exy- inverter is in a fault condition, 'xy' is the number of the Fault code,
example: E06.
0 to 800
Indicates the inverter output voltage in volt (V).
[ - ]
1 Vac
Indicates the torque developed by the motor. It is determined as follows:
0.0 to 150.0
[ - ]
0.1 %
Where:
Tm = Measured motor torque current
I
= Nominal motor torque current given by:
Tm
N = Speed
I
=
Tm
X = P410 x
0.0 to 3276
Indicates the instantaneous output power in kilowatt (kW).
[ - ]
0.1 kW
Indicates on the Keypad LCD display the status of the 6 digital inputs of
LCD = 1 or 0
the control board (DI1 to DI6), and the 2 digital inputs of the I/O Expansion
Board (DI7 and DI8). Number 1 stands for Active (DIx closed) and number
[ - ]
0 stands for Inactive (DIx open), in the following order:
-
DI1, DI2, ... , DI7, DI8.
The LED display shows a decimal value related to the 8 Digital Inputs,
where the status of each input is considered one bit of a binary number
where:
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Tm.100
P009 =
I
Tm
Y = 1 for N  Nrated
2
2
P401
- X
Y =
P178
100
x Y
Nrated
for N > Nrated
N