WEG CFW-09 User Manual page 167

Frequency inverter
Hide thumbs Also See for CFW-09:
Table of Contents

Advertisement

CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
P242
Analog Input AI3
Gain
(1)
P243
Analog Input AI3
Signal
P244
-100.0 to +100.0
Analog Input AI3
Offset
P245
Analog Input AI4
Gain (14 bit Analog
Input of the optional
board EBA. Refer to
chapter 8)
P246
(1)
Analog Input AI4
Signal
168
Range
Unit
Description / Notes
When parameters P237 = 2 and P241 = 2, the torque current limit (P169
and P170) is given by the signal at the Analog Input AI2.
When parameters P237 = 2 and P241 = 4, the torque current limit (P169
and P170) is given by the sum of the signals at Analog Inputs AI2 and
AI3.
When parameters P237 = 4 and P241 = 4, the torque current limit (P169
and P170) is given by the sum of the signals at Analog Inputs AI1 and
AI2.
Note: The range of the sum between AI2 and AI3 may vary from 0 to
180 %. If the sum result is negative, then the value will be set to zero.
0.000 to 9.999
Refer to P234.
[ 1.000 ]
0.001
0 to 3
[ 0 ]
-
When a current signal is used at the Analog Input AI3, set the S4.1
switch on the EBB board to "ON".
Options 2 and 3 provide an inverse reference with which is possible to
have maximum speed with minimum reference.
Refer to P234.
[ 0.0 ]
0.1 %
0.000 to 9.999
Refer to P234.
[ 1.000 ]
0.001
0 to 4
[ 0 ]
-
Input AI3 Signal
P243
(0 to 10) V / (0 to 20) mA
0
1
(4 to 20) mA
(10 to 0) V / (20 to 0) mA
2
3
(20 to 4) mA
Table 6.38 - AI3 signal selection
Input AI4 Signal
P243
0
(0 to 10) V / (0 to 20) mA
1
(4 to 20) mA
(10 to 0) V / (20 to 0) mA
2
3
(20 to 4) mA
(-10 to +10) V
4
Table 6.39 - AI4 signal selection
Switch S4.1 (EBB)
Off/On
On
Off/On
On
Switch S2.1 (EBA)
OFF/ON
ON
OFF/ON
ON
OFF