CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
174
Range
Unit
Description / Notes
- Speed = DIx Open (0 V), Torque = DIx Closed (+24 V).
When Torque is selected the speed regulators gains P161 and P162
are not used and changed to: Gp (Proportional Gain) = 1.00 and Gi
(Integral Gain) = 0.00. Thus the Total Reference becomes the input of
the Torque Regulator. Refer to figure 6.26.
When Speed is selected, the speed regulator gains are defined
again by P161 and P162. In applications with torque control, proceed
as described at P160.
- The Option DC Link Voltage Regulator must be used, when P150 = 2.
Refer to description of parameter P150.
- DI8 is designed to be used as Motor Thermistor (PTC) input on the
option boards EBA/EBB. It can also be used with just one PTC.
Temperature
increase
Temperature
decrease
- If DI8 should be used as normal digital input - Program the
parameter P270 to the required function and connect a resistor between
270  and 1600  in series with the input 4, as indicated below:
CONTACT
R = 270 to 1600 
XC4/XC5:
2
EBA/EBB
PTC
3
Inactive /
Without error
Inactive /
Without error
PTC resistance
oscillation
1k6
in ohms ()
Figure 6.33 - DI8 used as PTC input
XC4/XC5:
2
DI8
EBA/EBB
(P270)
3
Figure 6.34 - DI8 used as normal DI
DI8 (P270 = 16)
Inactive /
Active / E32
Without error
Active / E32
Active / E32
3k9
CONTACT
DI8
OPEN
DEACTIVATED
CLOSED
ACTIVATED