CHAPTER 5 - START-UP
DESCRIPTION
Self-tuning Mode Selection:
0 = No
1 = No Rotation
Enter the programming mode
Only select option 1 (No Rotation)
Self-tuning routine in progress
Motor Speed (rpm)
Motor accelerates from 0 to 90 rpm*
(Minimum Speed), in the Forward (CW)
(3)
direction of rotation
* for 4 pole motors
Motor accelerates up to 1800 rpm*
* for 4 pole motors
(2)
115