CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
P283
Time for RL2 ON
P284
Time for RL2 OFF
P285
Time for RL3 ON
P286
Time for RL3 OFF
186
Range
Unit
Description / Notes
Ix = P290 (Current Ix) - User selected current reference point.
Is = P003 (Motor Current).
Torque = P009 (Motor Torque).
Tx = P293 (Torque Tx) - User selected torque reference point.
Vpx = P533 (Process Variable x) - User selected reference point.
Vpy = P534 (Process Variable y) - User selected reference point.
Nt = Total Reference (Refer to figure 6.26) after all scalings, offsets,
additions, etc.
Hx = P294 (Hours Hx).
PLC = Refer to PLC board manual.
Fx = P370 (Frequency Fx) – Frequency reference defined by the user.
0.0 to 300
Used in the function as Relay Output: Timer of the relay 2 or 3.
[ 0.0 ]
When the timing function of the relays 2 and 3 is programmed at any
0.1 s
DIx, and when the transition is effected from 0 V to 24 V, the relay will
be enabled according to the time set at P283 (RL2) or P285 (RL3).
0.0 to 300
When the transition from 24 V to 0 V occurs, the programmed relay will
[ 0.0 ]
be disabled according to the time set at P284 (RL2) or P286 (RL3).
0.1 s
After the DIx transition, to enable or disable the programmed relay, it is
0.0 to 300
required that the DIx remains in on/off status during the time set at
[ 0.0 ]
parameters P283/P285 and P284/P286. Otherwise the relay will be reset.
0.1 s
Refer to figure 6.34.
Note: For this function, program P279 and/or P280 = 28 (Timer).
0.0 to 300
[ 0.0 ]
0.1 s