Setting Basic Application Parameters - WEG CFW-11 User Manual

Frequency inverter
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Step
Action/Result
11
- If needed, change the
value of P0298 according
to the inverter application.
To do so, press "Select"
This modification will affect
P0156, P0157, P0158,
P0401, P0404 and P0410
(this last one only if P0202
= 0, 1, or 2 – V/f control).
The time and the activation
level of the overload
protection will be affected
as well
13
- If needed, change the
value of P0400 according to
the motor rated voltage To
do so, press "Select"
This modification adjusts the
output voltage by a factor x
= P0400/P0296
15
- If needed, set P0402
according to the motor
rated speed. To do so, press
"Select". This modification
affects P0122 to P0131,
P0133, P0134, P0135,
P0182, P0208, P0288, and
P0289
17
- If needed, change the
value of P0404 according to
the motor rated power
To do so, press "Select"
This modification affects
P0410
19
- If needed, set P0406
according to the motor
ventilation. To do so, press
"Select"
- To complete the Oriented
Start-Up routine, press
"Reset" (left soft key) or

5.2.3 Setting Basic Application Parameters

After running the Oriented Start-up routine and properly setting the parameters, the inverter is ready to operate
in the V/f mode.
The inverter has a number of other parameters that allow its adaptation to the most different applications. This
manual presents some basic parameters that shall be set in most cases. There is a group named "Basic Application"
to make this task easier. A summary of the parameters inside this group is listed in
There is also a group of read only parameters that shows the value of the most important inverter variables such
as voltage, current, etc. The main parameters comprised in this group are listed in
For further details, please refer to the CFW-11 programming manual.
Display Indication
Config
0rpm
LOC
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Heavy Duty
Reset
13:48
Select
Config
0rpm
LOC
Motor Service Factor
P0398:
1.15
Motor Rated Voltage
P0400:
440 V
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Current
P0401:
13.5 A
Motor Rated Speed
P0402:
1750 rpm
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Frequency
P0403: 60 Hz
Motor Rated Power
P0404: 4hp 3kW
Reset
13:48
Select
Config
0rpm
LOC
Encoder Pulses Number
P0405:
1024 ppr
Motor Ventilation
P0406: Self-Vent.
Reset
13:48
Select
Figure 5.2 - Oriented Start-up
First Time Power-Up and Start-Up
Step
Action/Result
12
- If needed, change the
value of P0398 according
to the motor service factor
To do so, press "Select"
This modification will affect
the current value and the
activation time of the motor
overload function
14
- If needed, change the
value of P0401 according to
the motor rated current. To
do so, press "Select"
This modification will affect
P0156, P0157, P0158, and
P0410
16
- If needed, set P0403
according to the motor
rated frequency. To do
so, press "Select". This
modification affects
P0402
18
- This parameter will only be
visible if the encoder board
ENC1 is installed in the
inverter
- If there is an encoder
connected to the motor, set
P0405 according to the
encoder pulses number. To
do so, press "Select"
20
- After few seconds, the
display returns to the
monitoring mode
Display Indication
Config
0rpm
LOC
Application
P0298: Heavy Duty
Motor Service Factor
P0398:
1.15
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Voltage
P0400:
440V
Motor Rated Current
P0401:
13.5 A
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Speed
P0402:
1750 rpm
Motor Rated Frequency
P0403: 60 Hz
Reset
13:48
Select
Config
0rpm
LOC
Motor Rated Power
P0404:
4hp
3kW
Encoder Pulses Number
P0405:
1024 ppr
Reset
13:48
Select
Ready
0rpm
LOC
0
rpm
0.0
A
0.0
Hz
13:48
Menu
Table 5.1 on page
5-7.
Table 5.2 on page
5-8.
CFW-11 | 5-5