WEG CFW-09 User Manual page 55

Frequency inverter
Hide thumbs Also See for CFW-09:
Table of Contents

Advertisement

CHAPTER 3 - INSTALLATION AND CONNECTION
56
NOTE!
The wire sizing indicated in table 3.5 are reference values only. The exact
wire sizing depends on the installation conditions and the maximum
acceptable line voltage drop.
The tightening torque is as indicated in table 3.6. Use 75ºC copper wire
only.
CFW-09 Rating
A/Volts
6 A to 13 A/220-230 V
3.6 A to 13 A/380-480 V
16 A to 28 A/220-230 V
16 A to 24 A/380-480 V
2.9 A to 14 A/500-600 V
30 A/380-480 V
45 A/220-230 V
38 A to 45 A/380-480 V
22 A to 32 A/500-600 V
54 A to 86 A/220-230 V
60 A to 86 A/380-480 V
105 A to 130 A/220-230 V
105 A to 142 A/380-480 V
44 A to 79 A/500-600 V
180 A to 240 A/380-480 V
312 A to 600 A/380-480 V
107 A to 472 A/500-690 V
100 A to 428 A/660-690 V
Table 3.6 - Recommended tightening torque for power and
Line Fuses
For protecting the input rectifier diodes and the wiring, use UR Type
(Ultra-Rapid) fuses with i
Standard fuses may be used optionally at the input with currents as
indicated in table 3.5, or circuit breakers dimensioned for 1.2 x rated
inverter input current for the CT or the VT operation (refer to items 9.1.2
to 9.1.5).
However in this case, only the installation will be protected against short-
circuit, but not the diodes of the rectifier bridge at the inverter input. This
option may damage the inverter in case of short-circuit of some internal
component.
Grounding
Power Cables
Wiring
N.m (Ibf.in)
N.m (Ibf.in)
1.00 (8.85)
1.76 (15.58)
2.00 (17.70)
2.00 (17.70)
4.50 (39.83)
1.40 (12.30)
4.50 (39.83)
1.40 (12.30)
4.50 (39.83)
3.00 (26.10)
15.50 (132.75)
15.50 (132.75)
15.50 (132.75)
30.00 (265.50)
30.00 (265.50)
60.00 (531.00)
grounding connections
2
t equal or lower than indicated in table 3.5.