CHAPTER 3 - INSTALLATION AND CONNECTION
66
Connection 4 - FWD Run / REV Run
Selection function FWD/REV.
Parameters to be programmed:
Set DI3 to FORWARD Run
P265 = 8
Set DI4 to REVERSE Run
P266 = 8
When the FWD Run / REV Run Function is programmed, the function is
always active, in both local and remote operation modes.
At the same time, the keys
or P227 = 0)
The direction of rotation is defined automatically by the FWD Run / REV Run
commands.
Clockwise rotation for Forward and Counter Clockwise rotation for Reverse.
The speed reference can be from any source (as in Connection 3).
FWD Run S1
REV Run S2
Figure 3.17 - XC1 (CC9) wiring for connection 4
and
remain inactive (even when P224 = 0
Connector XC1
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
7
COM
8
COM
9
24 Vdc
10
GND

Hide quick links: