CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
(1)(10)
P204
Load/Save
Parameters
148
Range
Unit
Description / Notes
The parameters P295 (Inverter Rated Current), P296 (Inverter Rated
0 to 11
Voltage), P297 (Switching Frequency), P308 (Serial Address) and P201
[ 0 ]
(Language) are not changed when the factory default parameters are
-
loaded through P204 = 5 and 6.
In order to load the User Parameters #1 (P204 = 7) and/or the User
Parameters #2 (P204 = 8) into the operation area of the CFW-09, it is
necessary that the User Memory #1 and/or the User Memory #2 have
been previously saved (P204 = 10 and/or P204 = 11).
Once entered the user parameters are automatically saved to the VSD
EEPROM. In addition it is possible to save two further sets of
parameters, or to use these as a "backup".
The operation of Load User 1 and/or 2 can also be done by DIx (refer to
parameters P265 to P269).
The options P204 = 5, 6, 7, 8, 10 and 11 are disables when P309 0
(Active Fieldbus).
User
Default
1
Current
Factory
P204 = 5
Inverter
or 6
Default
Parameters
User
Default
2
Figure 6.23 - Parameter transference