CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
[Factory Setting]
Parameter
(1)
P308
Serial Address
(1)
P309
Fieldbus
P310
(1)
STOP Detection in a
Profibus Network
198
Range
Unit
Description / Notes
This feature prevents the motor from operating permanently at speeds
where the mechanical system enters into resonance, causing high
vibration or noise levels.
The passage through the skip speed band (2 x P306) is made at the
programmed acceleration/deceleration rates.
This function does not operate properly when two skip speeds are
overlapped.
1 to 30
Sets the address of the inverter for the serial communication. Refer to
[ 1 ]
item 8.13.
-
0 to 10
Defines the Fieldbus standard to be used (Profibus DP/DP-V1,
[ 0 ]
DeviceNet, EtherNet/IP or DeviceNet Drive Profile) and the number of
-
variables to be exchanged with the master. Refer to item 8.12.7.
It's only applicable if an optional Fieldbus communication kit were used.
0 or 1
This parameter allows programming the bit #6 of the Fieldbus control
[ 0 ]
word (refer to item 8.12.7.2 - Variable Written in the Inverter).
-
P309
Fieldbus Options
0
Inactive
1
Profibus DP/DP-V1 2 I/O
2
Profibus DP/DP-V1 4 I/O
3
Profibus DP/DP-V1 6 I/O
4
DeviceNet 2 I/O
5
DeviceNet 4 I/O
6
DeviceNet 6 I/O
7
EtherNet/IP 2 I/O
8
EtherNet/IP 4 I/O
9
EtherNet/IP 6 I/O
10
DeviceNet Drive Profile
Table 6.49 - Fieldbus options
NOTE!
If the PLC1 or PLC2 boards are used, the parameter P309
must be programmed as inactive.
P310
Function
Bit #6
0
Off
No function
If bit6 = 0
1
On
If bit6 = 1
Table 6.50 - STOP detection in a Profibus network
CFW-09 Action
-
Executes a General
Disable command,
regardless of the value of
the remaining bits of the
control word.
Executes the commands
that were programmed at
the remaining bits of the
control word.