CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
Line Termination
To avoid reflection, the initial and the end points of the network must be
terminated with the characteristic impedance. Thus a 120-ohms/0.5W resistor
must be connected between the pins 2 and 4 of the Fieldbus connector.
Baud Rate/ Node Address
There are three different baud rates for the DeviceNet: 125 kbits/s, 250 kbits/
s or 500 kbits/s. Choose one of these baud rates by setting the DIP switches
on the electronic board.
The node address is selected through the six DIP switches on the electronic
board, permitting an addressing from 0 to 63 addresses.
DIPs 1 and 2
Baud Rate [bits/s]
125 k
250 k
500 k
Reserved
Baud Rate
Address
ON
1
2 3
4
5
6 7 8
Figure 8.42 - Baud rate configuration an addressing to the DeviceNet
Configuration File (EDS File)
Each element of a DeviceNet network is associated to an EDS file that has all
information about the element. This file is used by program of the network
configuration during its configuration. Use the file with the extension .eds stored
on the floppy disk contained in the Fieldbus kit.
Setting parameter P309 to 4, 5 or 6 selects 2, 4 or 6 input/output words (refer
to item 8.12.7).
With the assistance of the network configuration software define the number
of words for the device according to the value set on parameter P309. The type
of connection used for data exchange shall be set for "Polled I/O".
NOTE!
The PLC (master) must be programmed for Polled I/O connection.
Signaling
The electronic board has a bicolor LED at right topside indicating the status of
the Fieldbus according to the table 8.16.
Address
00
0
01
1
10
2
11
61
62
63
1
0
DIP 3 to DIP 8
000000
000001
000010
111101
111110
111111