CHAPTER 3 - INSTALLATION AND CONNECTION
CC9 Board
Figure 3.13 - Dip switch position for
(0 to 10) V or (0 to 20) mA/(4 to 20) mA selection
As a default the analogue inputs are selected as (0 to 10) V. This can be
changed using the dip switch S1 on the control board.
Analog
Factory Default
Input
Function
AI1
Speed Reference
No Function
AI2
Table 3.7 - Dip switch configuration
Related Parameters: P221, P222, P234 to P240.
During the signal and control wire installation you must follow these
guidelines:
1) Cable Cross Section: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG );
2) Max. Torque: 0.50 N.m (4.50 lbf.in);
3) XC1 wiring must be connected with shielded cables and installed
separately from other wiring (power, control at 110 V/220 Vac, etc.),
according to table 3.8.
Inverter Model
Output current
 24 A
Output current
 28 A
Table 3.8 - Wiring separation distances
If the crossing of these cables is unavoidable, install them perpendicular,
maintaining a minimum separation distance of 5 cm (2 in) at the crossing
point.
* Can be used for grounding
of the signal
and control cable shields
Dip
Selection
Switch
OFF (0 to 10) V (Factory Default)
S1.2
ON (4 to 20) mA / (0 to 20) mA
OFF (0 to 10) V (Factory Default)
S1.1
ON (4 to 20) mA / (0 to 20) mA
Wiring
Min. Separation
Length
Distance
 100 m (330 ft)
 10 cm (4 in)
 25 cm (10 in)
> 100 m (330 ft)
 30 m (100 ft)
 10 cm (4 in)
 25 cm (10 in)
> 30 m (100 ft)
63