CHAPTER 5 - START-UP
ACTION
Press the
FWD / REV key
Obs.: The LEDs on the keypad
show whether the motor is running
FWD or REV
Press the
Stop key
Press the
key and hold it
Release the
key
116
LED DISPLAY
LCD DISPLAY
Motor Speed
P002 = 1800 rpm
VFD
ready
Motor Speed
P002 = 150 rpm
VFD
ready
NOTE!
The inverter always stores the last speed reference value set through the keypad.
Therefore, if you want to change this value before enabling the inverter use the
parameter P121 - Keypad Speed Reference.
NOTES!
(1) P401 maximum value is 1.8 x P295 for model 4.2 A/500-600 V and 1.6 x P295
for models 7 A and 54 A/220-230 V; 2.9 A and 7 A/500-600 V; 107 A, 147 A and
247 A/500-690 V; 100 A, 127 A and 340 A/660-690 V.
(2) The last speed reference value set via the
If you wish to change this value before enabling the inverter, change parameter
P121 (Keypad Reference).
(3) If the direction of rotation of the motor is inverted, power the inverter down, waits
10 minutes for the complete discharge of capacitors and interchange any two
motor output cables.
(4) In case of having E01 during deceleration, increase the deceleration time through
P101 / P103.
DESCRIPTION
(4)
Motor decelerates
down to 0 rpm
and then reverses the direction of
rotation accelerating back
1800 rpm
Motor decelerates down to 0 rpm
Motor accelerates from 0 rpm up to the
speed set at P122
Ex.: P122 = 150 rpm
CCW direction of rotation
Motor decelerates down to 0 rpm
and
keys is saved.
up to